Diesel power plant Dalgakiran DJ 17 BD-UA

Output power Unit. Meaning.
Backup power (StandBy – ESP) kVA / kW17 / 13,6
Rated power (Prime – PRP) kVA / kW15,5 / 12
Size W x D x H (mm) Weight (kg) Fuel tank (lt) Sound dB(A) @ 7m
Under the hood 750 x 1920 x 1240 650 70 N/A
Constant power Reserve capacity Rated power output
The maximum power that the generator set is capable of delivering continuously at an average load of up to 100%. Overloading is not allowed. Power at variable load for a limited time. Operation for 200 hours per year at an average load of 70%. It is used as a backup power supply in case of a power outage. Overload is not allowed. Constant power at variable load. The average load should not exceed 70%. 10% overload for 1 hour every 12 hours is allowed.

ENGINE

Manufacturer  FAW
Model.  4DW81-23D
Cylinder arrangement  IN-LINE
Number of cylinders  4
Volume л 2,27
Cylinder diameter mm 85
Piston stroke mm 100
Aspiration  Naturally aspirated
Regulator  Mechanical
Cooling system  Liquid
Lubricant volume л 7,8
Electrical system VDC 12
Speed / Frequency 50 Hz RPM 1500 rpm/ 50 Hz
Full sweat. Engine (Standby 50Hz) kV 19
Fuel consumption at load. 100% PRP g/kWh 240

ALTERNATOR

Model.  М20
Number of phases  3
Power factor  0,8
Voltage regulation  ± %0,5
Insulation class  H
Degree of protection  IP 23
Excitation system  Brushless
Frequency. Hz 50
Output voltage 50 Hz VAC 230 / 400
Rated power (in standby mode) 400_50 Hz kVA 20,3