EnEn

Diesel generator Dalgakiran DJ44BD SMART

Output power Unit. Meaning.
Reserve capacitykVA / kW44 / 35
Rated power outputkVA / kW40 / 32
SizeW x D x HWeight, kgFuel tank, lSound, dB
Under the hood1000 x 2150 x 15001000135N/A
Open1000 x 1700 x 1250800135N/A
Constant powerReserve capacityRated power output
The maximum power that the generator set is capable of delivering continuously at an average load of up to 100%. Overloading is not allowed. Power at variable load for a limited time. Operation for 200 hours per year at an average load of 70%. It is used as a backup power supply in case of a power outage. Overloading is not allowed.Constant power at variable load. The average load should not exceed 70%. 10% overload for 1 hour every 12 hours is allowed.
EngineUnit of measurement Meaning.
Manufacturer BAUDOUIN
Model. 4M06G44/5
Number of cylinders 4
Cylinder arrangement Ordnoye
Volumeл2.3
Piston strokemm92
Cylinder diametermm89
Aspiration NATURAL ASPIRATION
Regulator Electronic
Cooling system Liquid
The volume of the liquidл12.9
Lubricant volumeл9.5
Electrical systemVolt12
Speed / Frequency 50 HzRPM1500 rpm/ 50 Hz
Full motor power (Standby 50 Hz)kV41
Fuel consumption at load. %100 PRP 50Hz l/h9.3
Fuel consumption at load. %75 PRP 50Hz l/h6.8
Fuel consumption at load. %50 PRP 50Hz l/h4.6
GeneratorUnit of measurement Meaning.
Number of phases 3
Power factor 0,8
Number of bearings One
Number of poles 4
Voltage regulation (steady state) ± %1
Insulation class H
Degree of protection IP 23
Excitation system N/A
Connection type Phillips (Star)
Full harmonic harmonic efficiency – without nadir.  < %2,5
FrequencyHz50
Output voltage 50 HzVAC230 / 400
Rated power (in standby mode) 400_50 HzkVA44