Diesel generator Dalgakiran DJ275BD

| Output power | Unit. | Meaning. |
| Reserve capacity | kVA / kW | 275 / 220 |
| Rated power output | kVA / kW | 250 / 200 |
| Size | W x D x H | Weight, kg | Fuel tank, l | Sound, dB |
| Under the hood | 1300 x 3450 x 2000 | 2300 | 350 | 70 |
| Open | 1300 x 3000 x 1650 | 1950 | 350 | N/A |
| Constant power | Reserve capacity | Rated power output |
| The maximum power that the generator set is capable of delivering continuously at an average load of up to 100%. Overloading is not allowed. | Power at variable load for a limited time. Operation for 200 hours per year at an average load of 70%. It is used as a backup power supply in case of a power outage. Overload is not allowed. | Constant power at variable load. The average load should not exceed 70%. 10% overload for 1 hour every 12 hours is allowed. |
| Engine | Unit of measurement | Meaning. |
| Manufacturer | BAUDOUIN | |
| Model. | 6M16G275/5 (6M16G6D0/S) | |
| Number of cylinders | 6 | |
| Cylinder arrangement | Ordnoye | |
| Engine size | л | 9,73 |
| Piston stroke | mm | 130 |
| Cylinder diameter | mm | 126 |
| Aspiration | Turbocharge/Intercooler | |
| Regulator | Electronic | |
| Cooling system | Liquid | |
| The volume of the liquid | л | 50 |
| Lubricant volume | л | 22 |
| Electrical system | Volt | 24 |
| Speed / Frequency 50 Hz | RPM | 1500 rpm/ 50 Hz |
| Full motor power (Standby 50 Hz) | kV | 264 |
| Fuel consumption at load. %100 PRP 50Hz | l/h | 56.9 |
| Fuel consumption at load. %75 PRP 50Hz | l/h | 42.2 |
| Fuel consumption at load. %50 PRP 50Hz | l/h | 28,2 |
| Generator | Unit of measurement | Meaning. |
| Number of phases | 3 | |
| Power factor | 0,8 | |
| Number of bearings | One | |
| Number of poles | 4 | |
| Voltage regulation (steady state) | ± %1 | |
| Insulation class | H | |
| Degree of protection | IP 23 | |
| Excitation system | N/A | |
| Connection type | Phillips (Star) | |
| Full harmonic harmonic efficiency – without nadir. | < %2,5 | |
| Frequency | Hz | 50 |
| Output voltage 50 Hz | VAC | 230 / 400 |
| Rated power (in standby mode) 400_50 Hz | kVA | 275 |