Diesel generator Dalgakiran DJ220BD (SMART)

| Output power | Unit. | Meaning. |
| Reserve capacity | kVA / kW | 220 / 176 |
| Rated power output | kVA / kW | 200 / 160 |
| Size | W x D x H | Weight, kg | Fuel tank, l | Sound, dB |
| Under the hood | 1200 x 3150 x 1700 | 2455 | 335 | N/A |
| Open | 1200 x 3150 x 1600 | 2075 | 335 | N/A |
| Constant power | Reserve capacity | Rated power output |
| The maximum power that the generator set is capable of delivering continuously at an average load of up to 100%. Overloading is not allowed. | Power at variable load for a limited time. Operation for 200 hours per year at an average load of 70%. It is used as a backup power supply in case of a power outage. Overloading is not allowed. | Constant power at variable load. The average load should not exceed 70%. 10% overload for 1 hour every 12 hours is allowed. |
| Engine | Unit of measurement | Meaning. |
| Manufacturer | BAUDOUIN | |
| Model. | 6M16G220/5 | |
| Number of cylinders | 6 | |
| Cylinder arrangement | Ordnoye | |
| Volume | л | 9,73 |
| Piston stroke | mm | 130 |
| Cylinder diameter | mm | 126 |
| Aspiration | Turbocharge/Intercooler | |
| Regulator | Electronic | |
| Cooling system | Liquid | |
| The volume of the liquid | л | 50 |
| Lubricant volume | л | 24 |
| Electrical system | Volt | 24 |
| Speed / Frequency 50 Hz | RPM | 1500 rpm/ 50 Hz |
| Full motor power (Standby 50 Hz) | kV | 200 |
| Fuel consumption at load. %100 PRP 50Hz | l/h | 21,3 |
| Fuel consumption at load. %75 PRP 50Hz | l/h | 31,6 |
| Fuel consumption at load. %50 PRP 50Hz | l/h | 42,1 |
| Generator | Unit of measurement | Meaning. |
| Number of phases | 3 | |
| Power factor | 0,8 | |
| Number of bearings | One | |
| Number of poles | 4 | |
| Voltage regulation (steady state) | ± %1 | |
| Insulation class | H | |
| Degree of protection | IP 23 | |
| Excitation system | N/A | |
| Connection type | Phillips (Star) | |
| Full harmonic harmonic efficiency – without nadir. | < %2,5 | |
| Frequency | Hz | 50 |
| Output voltage 50 Hz | VAC | 230 / 400 |
| Rated power (in standby mode) 400_50 Hz | kVA | 220 |
| Equipment. | |
| BAUDOUIN diesel engine | ● |
| Alternator | ● |
| Radiator for engine cooling | ● |
| Rechargeable batteries with cables and terminals | ● |
| Electronic starter | ● |
| Charging generator for rechargeable batteries | ● |
| Automatic recharging of rechargeable batteries | ● |
| Automatic coolant heating | ● |
| Industrial silencer | ● |
| Three-pole circuit breaker | ● |
| Automatic control panel | ● |
| All-weather cover | ● |
| Automatic reserve input (ARI) | □ |
| Extended fuel tank | ○ |
| Monitoring | ○ |
| Trailer | ○ |
| Painting in a different color | ○ |
| Standard equipment: ● | Optional: □ | Optional equipment: ○ |